MODELING OF GRID TIED PV INVERTER TO IMPROVE ITS PERFORMANCE DURING UNBALANCE LOAD AND UNBALANCE FAULT

dc.contributor.authorDahal, Aashish
dc.contributor.authorKhanal, Bibek
dc.contributor.authorBhattarai, Kulchandra
dc.contributor.authorShrestha, Lenish
dc.date.accessioned2023-08-21T07:11:22Z
dc.date.available2023-08-21T07:11:22Z
dc.date.issued2023-04
dc.descriptionThis project aims the study of problems in the operation of inverter during unbalance load and unbalance fault condition along with the possible control measures to mitigate those problems to ensure the safe and reliable operation of the inverter.en_US
dc.description.abstractWith the demand of alternative source of energy, there is an increasing trend in solar power plants, as it is abundant, clean and has significantly reduced the reliance on conventional energy sources. Integrating solar through inverter brings about various challenges in the microgrids and the inverter itself. This project aims the study of problems in the operation of inverter during unbalance load and unbalance fault condition along with the possible control measures to mitigate those problems to ensure the safe and reliable operation of the inverter. A grid connected PV inverter is modeled using hysteresis band controller and implementing the MPPT of the PV system with the buck boost converter. During unbalance load and unbalance fault condition, the negative and zero sequence components of current exists. All the zero-sequence component of current is delivered by the grid. The negative sequence component of current also flows through the inverter resulting in high value of current and loss of stability. Also, the voltage across the dc link capacitor increases during voltage dip. The high value of current flowing through the inverter and high voltage across dc link capacitor may damages the inverter and capacitor respectively.en_US
dc.identifier.urihttps://hdl.handle.net/20.500.14540/19253
dc.language.isoenen_US
dc.publisherI.O.E. Pulchowk Campusen_US
dc.subjectPV INVERTER,en_US
dc.subjectSolar energyen_US
dc.subjectInverteren_US
dc.titleMODELING OF GRID TIED PV INVERTER TO IMPROVE ITS PERFORMANCE DURING UNBALANCE LOAD AND UNBALANCE FAULTen_US
dc.typeReporten_US
local.academic.levelBacheloren_US
local.affiliatedinstitute.titlePulchowk Campusen_US
local.institute.titleInstitute of Engineeringen_US
Files
Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
6. MODELING OF GRID TIED PV INVERTER TO IMPROVE ITS.pdf
Size:
5.29 MB
Format:
Adobe Portable Document Format
Description:
License bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.71 KB
Format:
Item-specific license agreed upon to submission
Description: