Optimal Network Reconfiguration and Distributed Generation Integration for Power Loss Minimization and Voltage Profile Enhancement in Radial Distribution System

dc.contributor.authorManandhar, Naresh
dc.date.accessioned2023-07-04T04:41:39Z
dc.date.available2023-07-04T04:41:39Z
dc.date.issued2022-09
dc.descriptionNetwork Reconfiguration with Distributed Generation (DG) integration can significantly reduce power loss and improve the system voltage. This thesis explores the approach for reduction in power loss and improvement in system voltage through a combination of network reconfiguration and DG installation in radial distribution systems.en_US
dc.description.abstractNetwork Reconfiguration with Distributed Generation (DG) integration can significantly reduce power loss and improve the system voltage. This thesis explores the approach for reduction in power loss and improvement in system voltage through a combination of network reconfiguration and DG installation in radial distribution systems. Initially, the approach was verified in a typical 33 and 69 Test Bus system in MATLAB using the Backward/Forward Propagation Load Flow approach. Voltage Stability Index (VSI) technique has been applied to determine the most sensitive bus to locate for DG integration. Artificial Bee Colony (ABC) algorithm was used to determine the optimal solution. Six scenarios for different combinations of system reconfiguration and DG installation were analyzed by using NEA 63-Bus real distribution network of the Nepal Electricity Authority (NEA), Kirtipur Distribution Center. The simulated results were compared with the base case scenario and were validated with results from the previous studies for DGs injecting active power only. Among them, Scenario VI (simultaneous network reconfiguration and DG integration) gave the best result for power loss reduction and voltage profile improvement. The results obtained in this study show that, for DGs generating active power only, the percentage reduction in active or real power has been improved by 72.19%, 83.52%, and 57.69% for the IEEE 33, IEEE 69, and NEA 63-Bus system respectively. Similarly, for DGs generating both real and reactive power, the power loss has been reduced by 91.61%, 96.53%, and 90.54% for the IEEE 33,en_US
dc.identifier.urihttps://hdl.handle.net/20.500.14540/18382
dc.language.isoenen_US
dc.publisherI.O.E. Pulchowk Campusen_US
dc.subjectNetworken_US
dc.subjectVoltageen_US
dc.subjectPoweren_US
dc.titleOptimal Network Reconfiguration and Distributed Generation Integration for Power Loss Minimization and Voltage Profile Enhancement in Radial Distribution Systemen_US
dc.typeThesisen_US
local.academic.levelMastersen_US
local.affiliatedinstitute.titlePulchowk Campusen_US
local.institute.titleInstitute of Engineeringen_US
Files
Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Naresh Manandhar energy systems planning and management 2022.pdf
Size:
2.02 MB
Format:
Adobe Portable Document Format
Description:
License bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.71 KB
Format:
Item-specific license agreed upon to submission
Description: