Potential determination, performance and voltage profile analysis of grid connected roof-top solar PV at Bishnumati Distribution Feeder

dc.contributor.authorPoudel, Padam Raj
dc.date.accessioned2022-04-25T08:57:26Z
dc.date.available2022-04-25T08:57:26Z
dc.date.issued2022-03
dc.descriptionThis thesis presents the solar roof-top photo-voltaic generation capacity at Bishnumati feeder of Balaju Distribution Control System (DCS) with its performance and voltage profile analysis during grid connection by considering eleven potential commercial and non-commercial buildingsen_US
dc.description.abstractThis thesis presents the solar roof-top photo-voltaic generation capacity at Bishnumati feeder of Balaju Distribution Control System (DCS) with its performance and voltage profile analysis during grid connection by considering eleven potential commercial and non-commercial buildings. The Building Foot-Print Area (BFA) obtained is 8915.13 m2 and the actual photo-voltaic area (PVA) is 4190.11 m2, which is used to install the solar module in the roof of the selected buildings. PVsyst is used for performance analysis, the energy generated by solar array (E_array) and energy supplied to the grid (E_grid) is 1018.319 MWh and 982.039 MWh per year respectively. The performance ratio over the year is 0.74. The average capacity factor of overall installation is obtained as 17 %. ETAP is used for feeder modeling and load flow analysis. Form load flow analysis the minimum grid voltage before solar PV injection is 10.32 kV at a nominal bus voltage of 11 kV. After injection of solar PV into the grid, the minimum bus voltage is improved to 10.53 kV.en_US
dc.identifier.citationMASTER OF SCIENCE IN RENEWABLE ENERGY ENGINEERINGen_US
dc.identifier.urihttps://hdl.handle.net/20.500.14540/9987
dc.language.isoenen_US
dc.publisherPulchowk Campusen_US
dc.subjectPhotovoltaicen_US
dc.subjectSolaren_US
dc.subjectVoltageen_US
dc.titlePotential determination, performance and voltage profile analysis of grid connected roof-top solar PV at Bishnumati Distribution Feederen_US
dc.typeThesisen_US
local.academic.levelMastersen_US
local.affiliatedinstitute.titlePulchowk Campusen_US
local.institute.titleInstitute of Engineeringen_US
Files
Original bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
Potential determination, performance and voltage profile analysis of grid connected roof-top solar PV at Bishnumati Distribution Feeder.pdf
Size:
2.26 MB
Format:
Adobe Portable Document Format
Description:
License bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.71 KB
Format:
Item-specific license agreed upon to submission
Description: